Dehumidification >> What Is A Normal Dehumidifier Setting In Degrees

Recuperative heat exchange is a universal technology applicable to vapor-compression, direct-expansion, and chilled-water air-handling-unit (AHU) coils; heat-powered desiccant dehumidification equipment; dehumidifiers; supermarket, ice-rink, and natatorium air-conditioning and dehumidification systems; and packaged 100-percent-outside-air conditioners. This installment discusses five types of What Is A Normal Dehumidifier Setting In Degrees recuperative sensible-heat exchangers that are used to prevent over cooling while still meeting the dehumidification needs of a conditioned space.
 
 The energy aspects of this technology are explained in great What Is A Normal Dehumidifier Setting In Degrees detail. The reason for this is that many owners and designers are under the incorrect assumption that there are no penalties associated with the use of hot-gas or condenser-water reheat. This is not to say that one should always use some form of recuperative heat exchange in preference to hot-gas or condenser water reheat.
 
It simply is to say that owners and designers should be aware that there is a more energy-efficient way to accomplish reheat while also What Is A Normal Dehumidifier Setting In Degrees reducing the required cooling capacity. Also addressed in this installment are the four penalties associated with ordinary "new-energy” reheat and a technology that is used to avoid one of those penalties: reheat using hot refrigerant gas.
 
RECUPERATIVE DEHUMIDIFICATION
 Recuperative-dehumidification enhancements are good solutions for 100-percent-outside-air cooling units. Five such enhancements are: 1) Coil-loop run-around precooling and What Is A Normal Dehumidifier Setting In Degrees reheating coils (water or glycol). 2) Heat-pipe run-around precooling and reheating coils. 3) Air-to-air flat-plate heat exchangers for precooling and reheating. 4) Rotary-wheel heat exchangers for precooling and reheating. 5) Refrigerant liquid subcooling/airreheating coil.
 
Each of the first four enhancements involves one heat-transfer device located upstream from the main cooling coil and one heat-transfer device located downstream from the main cooling coil. The What Is A Normal Dehumidifier Setting In Degrees upstream device precools air as it enters the main cooling coil, while the downstream device reheats the air by the same enthalpy change as it leaves the main cooling coil. Other than a small increase in fan energy to overcome the added air friction of the precooling and reheating sections and a fractional-hp pump for the coil-loop enhancement, no external energy is used.
 
 (If the heattransfer devices are active for only a small portion of the annual operating hours, consider bypass dampers to reduce the annual energy impact.) The first four enhancements can be applied to any type of primary cooling coil: chilled water, chilled What Is A Normal Dehumidifier Setting In Degrees glycol, or refrigerant. If the primary coil is of the refrigerant type, then the performance of the refrigeration system must be verified at mild- and cool-weather entering-air conditions to ensure that the refrigeration system will operate without compressor cycling or liquid slugging and with proper oil return.
 
 Suction temperatures above 30 F are necessary to prevent frost or ice accumulation on the main cooling coil. The performance of 100-percentoutside-air recuperative-dehumidification What Is A Normal Dehumidifier Setting In Degrees enhancements varies from a maximum temperature change at peak cooling conditions to no temperature change at an outside temperature of approximately 50 F. This performance usually is acceptable because the latent load of the outside air declines with outside temperature.
 
Applications must be analyzed to determine if additional reheat (from hot refrigerant gas, electric heating coils, thermal heating coils, or in-space heat sources) is required to maintain acceptable space conditions. Supplementary reheat coils, if required, must be located What Is A Normal Dehumidifier Setting In Degrees downstream from the recuperative-dehumidification reheat coil. Heating, recuperative-reheat, and conventional reheat coils must be separated from the main cooling coil to allow condensed moisture to drain from the main cooling coil without being re-evaporated by radiant or conducted heat.
 
 The main cooling coil must be selected at a coil face velocity at least 150 fpm below the maximum cataloged face velocity to ensure What Is A Normal Dehumidifier Setting In Degrees that moisture does not carry over onto a reheat coil (liquid water carryover onto an active reheat coil results in additional energy consumption and humidification). AHU fans and motors (if the motor is in the air stream) should be located downstream from the recuperative reheat system for optimum effectiveness.
 
If a supplementary reheat coil is used and its leaving-air temperature is above 100 F, then the fan motor must be selected for reliable operation at the actual temperature conditions at the motor. It may be necessary to de-rate the motor and use Class F or H high What Is A Normal Dehumidifier Setting In Degrees temperature motor-winding insulation. Special motors are not required for recuperative-reheat systems not equipped with supplementary reheat coils. Because of the possibility of moisture condensing on precooling heat-transfer surfaces during part-load operating conditions, provisions for collecting and draining condensate must be made.
 
 Heat-exchange surfaces will accumulate particulate even with well maintained filters. Surfaces should be accessible and cleanable without difficulty or high cost. The fifth recuperative-dehumidification enhancement is superior to the other four in many respects because it achieves almost the same result with a single coil located What Is A Normal Dehumidifier Setting In Degrees downstream from the main cooling coil. The single coil reduces first cost, halves the air-side friction of the recuperative elements, and requires no space or modifications upstream from the main cooling coil.
 
With the fifth enhancement, which is applicable only to systems using refrigerant coils served by compressors, the amount of What Is A Normal Dehumidifier Setting In Degrees reheat is limited. If a significant temperature rise is required, this enhancement may need to be combined with one of the other four. Details on each of the five recuperative-dehumidification enhancements follow.
 
 COIL-LOOP RUN-AROUND PRECOOLING, REHEATING
Run-around coils for enhanced dehumidification systems are not a new technology. They are well-described in texts from as long ago as 1939.1, 2, 3, 4 The psychrometric-chart analysis of run-around coils for precooling and reheating is identical to that for What Is A Normal Dehumidifier Setting In Degrees ordinary reheat (see sidebar) with one exception: The precooling coil cools the entering air from 84- to 72-F dry bulb (DB); therefore, the air entering the main cooling coil is cooler, which means that the main cooling coil does not have to remove as much heat.
 
The reheat is provided not by an external source of expensive energy, but by the heat picked up by the circulating fluid in the precoil. The cycle and savings are illustrated in Figure 2. Figure 3 is a What Is A Normal Dehumidifier Setting In Degrees piping diagram showing that run-around coils require a small closed-loop piping system. When freezing is a possibility, the heat-transfer fluid is dilute ethylene glycol; at other times, it is water.

How To Prevent Sewer System Backup

Having sewage back up into the home is an unpleasant and potentially unhealthy experience. The information contained here can help protect you from the hazards of raw sewage in your basement and give you practical methods for proper sanitation of your building should a back-up occur.
Sewers ca  read more..

Get An Asbestos Certification In Pennsylvania

Asbestos Removal, testing Collection Procedure: Collect approximately 1 to 2 grams of each type of material and place into separate 20 mL scintillation vials. Analytical Procedure. A portion of each separate phase is analyzed by gross examination, phase-polar examination, and Asbestos Abatement Get An Asbestos Certification In Pennsylvania central   read more..

Flash Floods Mold And Mildew

Following a widespread flooding disaster, many questions arise from citizens within the communities affected and from the many volunteers and Flood Damage Flash Floods Mold And Mildew organizations that are working in the devastated area. Personal health and safety is a priority for everyone.

The following information i  read more..

How To Dehumidify A Water Damaged House

Dehumidification with Climate Changer™ Air Handlers Triple the amount of water removed The Trane ™ desiccant dehumidification system is Dehumidification How To Dehumidify A Water Damaged House an award winning method for controlling space humidity. A desiccant wheel is configured in series with the cooling coil to significantly improv  read more..

Water Damage

A dampness in your home is usually the result from a water incursion either from an internal source, like leaking water pipes or an external sources, such as rainwater due to some kind of storm damage. The intrusion of the dampness becomes a real problem when the various materials in your bui  read more..

Remove The Musty Smell From A Basement After Water

Exterior wall insulation must be approved for below-grade use. Typically, three products are used below grade: extruded polystyrene, expanded polystyrene, and rigid mineral fiber panels. (Baechler et al. 2005). Basement Drying Remove The Musty Smell From A Basement After Water Extruded polystyrene (nominal R-5 per inch) is a common choice.    read more..

How To Clean Fire Smoke Damage

Tips on how to handle the fire damage There are companies that are experts in cleaning and/or restoring your personal items.Whether you or your insurer buys this type of fire service, Fire Damage How To Clean Fire Smoke Damage be clear on who will pay for it. 

Be sure to ask for an estimate of cost for t  read more..

Wind Damage To Trees

Wind damage to trees AL FERRER SEMINOLE COUNTY URBAN HORTICULTURIST The impact of hurricanes on trees varies from simple defoliation to broken branches, split branch crotches and trunks, leaning or falling trees. While no tree can be guaranteed to stand up to hurricane-force winds, there are some tr  read more..

How To Treat Water Damaged Carpet

Science Plan identifies specific scientific and technical programmatic issues of current importance to Ohio and the Nation. An examination of those issues yielded a set of five major focus areas with associated science goals and strategies that the Ohio Water Science Center will emphasize in its&nbs  read more..

What Is Black Mold

Mold problems in buildings are a result of water and moisture problems. Renters need to operate the heating and ventilation systems to reduce water condensation. Renters need to notify landlords promptly, in writing, of any water leaks or moisture problems. If there is a water leak or moisture probl  read more..