Wind Damage >> Withstanding Wind And Lightning

Rooftop Attachment of Lightning Protection Systems in High-Wind Regions Hurricane Katrina Recovery AdvisoryFEMA May 2006, Revised July 2006 Purpose: To recommend practices for installing lightning protection systems (LPS) that will enhance Withstanding Wind And Lightning wind resistance in high-wind regions. Key Issues 

Lightning protection systems frequently become disconnected from rooftops during hurricanes. Displaced LPS components can puncture and tear roof coverings, Withstanding Wind And Lightning thus allowing water to leak into buildings (see Figures 1 and 2). 

Also, when displaced, Withstanding Wind And Lightning the LPS is no longer capable of providing lightning protection in the vicinity of the displaced conductors ("cables”) and air terminals ("lightning rods”). Figure 1 caption: This displaced air terminal punctured the membrane in several locations. [end of Figure 1 caption] 

Figure 2 caption: View of an abraded end of a conductor that became disconnected. [end of Figure 2 caption] Lightning protection standards such as NFPA 780 and Withstanding Wind And Lightning UL 96A currently provide inadequate guidance for attachment of LPS to rooftops in high-wind regions. 

Some LPS manufacturers provide guidance for attachment, while other manufacturers refer to the roofing material manufacturer for attachment guidance. Some roofing material manufacturers provide guidance for attachment, Withstanding Wind And Lightning while other manufacturers refer to the LPS manufacturer for attachment guidance. 

In most cases, the attachment guidance provided by LPS and roofing material manufacturers is inadequate for hurricane-prone regions. LPS conductors are typically attached to the roof at 3 foot intervals. Because the conductors are flexible, Withstanding Wind And Lightning when they are exposed to high winds, the conductors exert dynamic loads on the conductor connectors ("clips”). 

Guidance for calculating the dynamic loads does not exist. The attachment guidance that follows is therefore based on professional judgment. LPS conductor connectors typically have prongs to anchor the conductor. When the connector is well-attached to the roof surface, Withstanding Wind And Lightning during high winds the conductor frequently bends back the malleable connector prongs. 

Conductor connectors have also debonded from roof surfaces during high winds. Based on observations after Hurricane Katrina and other hurricanes, Withstanding Wind And Lightning it is apparent that pronged conductor connectors do not provide reliable attachment. Figure 3 caption: During high winds, the conductor deformed the prongs and pulled away from this conductor connector. 

Construction Guidance Parapet attachment: When the parapet is 12-inch high or greater, Withstanding Wind And Lightning it is recommended that the air terminal base plates and conductor connectors be mechanically attached with #12 screws that have 1.25 inch minimum embedment into the inside face of the parapet nailer and properly sealed for watertight protection. 

In lieu of conductor connectors that have prongs, it is recommended that mechanically attached looped connectors be installed (see Figure 4). Figure 4 caption: This conductor was attached to the coping with a looped connector (above). However, Withstanding Wind And Lightning a gasket was not installed between the connector and the coping. 

Also, because the connector screws were too short to engage the wood nailer, the screws pulled out and the conductor was displaced in some areas (figure at left). [end of Figure 4 caption] Attachment to built-up, Withstanding Wind And Lightning modified bitumen and single-ply membranes: For built-up and modified bitumen membranes, attach air terminal base plates with asphalt roof cement. 

For single-ply membranes, attach air terminal base plates with pourable sealer (type recommended by the membrane manufacturer). In lieu of attaching conductors with conductor connectors, Withstanding Wind And Lightning it is recommended that conductors be attached with strips of membrane installed by the roofing contractor. 

For built-up and modified bitumen membranes, use strips of modified bitumen cap sheet, approximately 9-inch wide minimum. For single-ply membranes, use self-adhering flashing strips, Withstanding Wind And Lightning approximately 9” wide minimum. If strips are torch-applied, avoid overheating the conductors. Start the strips approximately 3 inches from either side of the air terminal base plates. 

Place strips that are approximately 3’ long, followed by a gap of approximately 3 inches (see Figure 5). Figure 5 caption: Plan showing conductor attachment. [end of Figure 5 caption] [text box]Note: As an option to securing the conductors with stripping plies, Withstanding Wind And Lightning conductor connectors that do not rely on prongs (such as the one shown in Figure 6) could be used.

However, because the magnitude of the dynamic loads induced by the conductor are unknown and because of the lack of data on the resistance provided by adhesively-attached connectors, Withstanding Wind And Lightning attachment with stripping plies is the preferred option because the stripping plies shield the conductor from the wind. 

Figure 6 caption: Adhesively-attached conductor connector that does not use prongs. [end of Figure 6 caption] If adhesive-applied conductor connectors are used, Withstanding Wind And Lightning it is recommended that they be spaced more closely than the 3 foot spacing required by NFPA 780 and UL 96A. 

Depending upon wind loads, spacings in the range of 6 to 12 inches on center may be needed in the corner regions of the roof, Withstanding Wind And Lightning with spacings in the range of 12 to 18 inches on center at roof perimeters (see ASCE 7 for size of corner regions).[end of text box] Mechanically Attached Single-Ply Membranes: 

It is recommended that conductors be placed parallel and within 8 inches of membrane fastener rows. Where the conductor falls between or is perpendicular to membrane fastener rows, Withstanding Wind And Lightning install an additional row of membrane fasteners where the conductor will be located and install a membrane cover-strip over the membrane fasteners. 

Place the conductor over the cover-strip and secure the conductor as recommended above. Note: By following the above recommendations, Withstanding Wind And Lightning additional rows of membrane fasteners beyond those needed to attach the membrane may be needed to accommodate layout of the conductors. 

The additional membrane fasteners and cover-strip should be coordinated with and installed by the roofing contractor. Standing Seam Metal Roofs: It is recommended Withstanding Wind And Lightning that pre-manufactured mechanically attached clips that are commonly used to attach various items to roof panels be used. 

After anchoring the clips to the panel ribs, the air terminal base plates and conductor connectors are anchored to the panel clips. In lieu of conductor connectors that have prongs, Withstanding Wind And Lightning it is recommended that mechanically attached looped connectors be installed. Conductor Splice Connectors: 

In lieu of pronged splice connectors (see Figure 7), bolted splice connectors are recommended (see Figure 8). It is recommended that strips of flashing membrane (as recommended above) be placed approximately 3 inches from either side of the splice Withstanding Wind And Lightning connector to minimize conductor movement and avoid the possibility of the conductors from becoming disconnected. 

To allow for observation during maintenance inspections, do not cover the connectors. Periodic Inspection and Maintenance: Each spring, it is recommended that the lightning protection system be inspected to verify that connectors are Withstanding Wind And Lightning still attached to the roof surface and still engage the conductors. Also check to ensure that splice connectors are still secure. Inspections are also recommended after high wind events.

Wet Carpet From Basement Flood

What is mold? Mold is a general term used to describe a type of fungus. There are many different types of molds and they are common throughout nature. Molds may vary in color and appearance. Some molds may be seen on foods, damp surfaces, cloth and other porous materials, Water Damage Wet Carpet From Basement Flood and may be r  read more..

How To Remove The Mildew Smell From A Flooded Base

Backhoes (power shovels) are available in a wide range of sizes, down to small "walk-behind” units capable of maneuvering in tight spaces like residential lots. Full foundation excavation with conventional backhoes is the base Basement Drying How To Remove The Mildew Smell From A Flooded Base case. Along with high cost, this method leads to very large im  read more..

Dealing With Frozen Pipes

Keep open cabinet doors leading to exposed pipes (such as access doors for sinks), so that household air can warm them.The natural flow of warmer air will help combat many problems.If you have an attached garage, keep its doors shut.Occasionally, plumbing is routed through this unheated space, Water Damage Dealing With Frozen Pipes&  read more..

Natural Disaster Safety Tips

You may be surprised by what you find when you get back home after a flood. Water may still be standing in your yard or your house. Many of your belongings may be damaged Water Damage Natural Disaster Safety Tips or destroyed. There will be changes in your house, your yard and your neighborhood. Some of those changes may hurt  read more..

Guidelines For Cleaning Up Raw Sewage

Floods can cause damage to floors, walls, rugs and personal belongings. After a flood, it is important to clean and dry affected items as quickly as possible to prevent mold growth. If flood waters contain sewage, Sewage Cleanup Guidelines For Cleaning Up Raw Sewage it is important to disinfect contaminated items and to keep yourself from coming   read more..

How To Clean A Former Meth Lab Property

Cooking methamphetamine, (meth), results in the release of ingredient chemicals, the precursor drugs (pseudoephedrine or ephedrine), meth in vapor and particle form and other largely unknown byproducts Meth Lab Cleanup How To Clean A Former Meth Lab Property regardless of the cooking method used.Airborne contaminants are absorbed into soft   read more..

Flooded Basement

It's laundry day, you round up your clothes and you start to head to the basement as you're getting close you start to hear a hissing sound. You think to yourself, that's a sound I've never heard before you also think, when was the last time I went in the basement. As you round the corner and   read more..

How To Clean Up Smoke And Soot From A Fire

How to Clean Up Smoke and Soot from a Fire Smoke and soot can travel and penetrate into other rooms affecting paint, carpet,upholstery, drapes, clothing and any other belongings. Ventilation of the fire scene or debris removal is an effective first step to clean up after fire. Thorough cleaning and   read more..

Tornado Damage

During a typhoon, houses might get wind damage or destroyed by high wind damage and high undulations. Debris could smash windows and doors, permitting high wind damage inside the house. In tremendous storms, such as Typhoon Andrew, the force of the Wind Damage Tornado Damage alone could cause weak spots in your ho  read more..

Storm Damage

If your home has sustained a significant amount of Dehumidification Storm Damage because the roof was damaged and the rainwater leaked through. There is a certain procedure that should be followed to minimize the possibility of any other damage like the growth of mold or any other structural damage. Your home should   read more..